Breaker Size to Wire Size Chart (15 to 200 Amps)

By Hassan Nawaz, B.Sc. Electrical Engineering. Updated November 11, 2026.

Find your breaker rating in the first column and read across for the smallest copper or aluminum wire the NEC allows. A 100 amp wire size chart or a 40 amp one is the same table, different row. For long runs, use the wire size calculator, because voltage drop can require a larger wire.

Minimum wire size by breaker rating

The smallest wire size whose NEC Table 310.16 ampacity is at least the breaker rating, with the small-conductor limits of 240.4(D). The 60°C column applies to NM-B (Romex) cable and to equipment with 60°C terminals. The 75°C column applies to THHN or THWN wire in conduit on 75°C-rated terminals.

BreakerCopper, 60°C / NM-BCopper, 75°CAluminum, 75°CAluminum, 60°C
15 A14 AWG14 AWG12 AWG12 AWG
20 A12 AWG12 AWG10 AWG10 AWG
25 A10 AWG10 AWG10 AWG10 AWG
30 A10 AWG10 AWG8 AWG8 AWG
35 A8 AWG8 AWG8 AWG6 AWG
40 A8 AWG8 AWG8 AWG6 AWG
45 A6 AWG8 AWG6 AWG4 AWG
50 A6 AWG8 AWG6 AWG4 AWG
60 A4 AWG6 AWG4 AWG3 AWG
70 A4 AWG4 AWG3 AWG2 AWG
80 A3 AWG4 AWG2 AWG1 AWG
90 A2 AWG3 AWG2 AWG1/0 AWG
100 A1 AWG3 AWG1 AWG1/0 AWG
110 A1 AWG2 AWG1/0 AWG2/0 AWG
125 A1/0 AWG1 AWG2/0 AWG3/0 AWG
150 A3/0 AWG1/0 AWG3/0 AWG4/0 AWG
175 A4/0 AWG2/0 AWG4/0 AWGn/a
200 An/a3/0 AWGn/an/a

Sizes are minimums for ampacity. Add distance, a hot location, bundled circuits or continuous loads, and the wire may need to go up.

Guides for the most common breakers

Continuous loads

Loads that run for three hours or more, such as EV chargers and some heaters, must be sized at 125% of the load. A 32 A charger needs a 40 A circuit, and a 40 A charger needs a 50 A circuit. Pick the wire for the breaker, not the charger.

Ground wire

The equipment ground is sized from the breaker as well, using NEC Table 250.122: 14 AWG copper for 15 A, 12 AWG for 20 A, 10 AWG for 30 to 60 A and 8 AWG for 70 to 100 A. See the ground wire size calculator.

Frequently asked questions

What size wire for a 100 amp breaker?

3 AWG copper or 1 AWG aluminum at 75°C. A 100 amp dwelling service may use 4 AWG copper under NEC 310.12.

What size wire for a 30 amp breaker?

10 AWG copper, or 8 AWG aluminum.

Can I put a 20 amp breaker on 14 gauge wire?

No. 14 AWG copper is limited to a 15 amp breaker. Use 12 AWG for 20 amps.

What size wire for a 60 amp breaker?

6 AWG copper at 75°C, or 4 AWG for NM-B cable or 60°C terminals.

Sources

Calculators for this

Last updated November 11, 2026. Values follow published tables. How we check our data. Found an error? Tell us.