Conduit Fill Calculator

By Hassan Nawaz, B.Sc. Electrical Engineering. Updated November 11, 2026.

Pick the conduit type and trade size, then the wire size and count. The calculator returns the fill percentage, the NEC Chapter 9 limit and the most conductors of that size the conduit allows.

Count every conductor, including grounds.
39.4%
Conduit fill
40%
NEC limit
9
Max wires this size
Pass
Result

NEC conduit fill rules

NEC Chapter 9, Table 1 limits how much of a conduit's internal area conductors can occupy, so wires can be pulled without damage and heat can escape:

Number of conductorsMaximum fill
153%
231%
3 or more40%

Fill % = (number of wires × wire area) ÷ conduit internal area × 100

Conduit areas come from Chapter 9, Table 4, and THHN/THWN-2 conductor areas from Table 5. For example, nine 12 AWG THHN wires (0.0133 in² each) in 1/2" EMT (0.304 in²) fill 39.4%, just under the 40% limit. That matches Annex C, which allows nine.

Internal area (in²)

Trade sizeEMTPVC Sch 40
1/2"0.3040.285
3/4"0.5330.508
1"0.8640.832
1-1/4"1.4961.453
1-1/2"2.0361.986
2"3.3563.291

NEC Chapter 9, Note 7 lets you round up when the calculated number of same-size conductors has a decimal of 0.8 or more, which is why the maximum can sit slightly above 40%.

Fill is not ampacity. More than three current-carrying conductors in one raceway also triggers ampacity derating under NEC 310.15(C)(1). Run the wire size calculator and apply the adjustment factor separately.

Conduit fill chart

The full chart of maximum wires per conduit size, for EMT and PVC, is on the conduit fill chart page, with a table of the smallest conduit for 2 to 12 wires.

How many 12 gauge wires fit in 3/4 inch conduit?

Sixteen 12 AWG THHN conductors in 3/4-inch EMT, or fifteen in 3/4-inch Schedule 40 PVC. More than three current-carrying conductors in one raceway also triggers ampacity derating, so check the wire size after you fill the conduit.

Frequently asked questions

How many 12 AWG wires fit in 1/2 inch EMT?

Nine THHN conductors, which brings the fill to 39.4% of the 40% limit.

Do grounding wires count toward fill?

Yes. Equipment grounding conductors count toward fill, though they do not count as current-carrying conductors for derating.

Does conduit fill apply to short nipples?

A nipple 24 inches or shorter may be filled to 60% under Chapter 9, Note 4, and derating does not apply to it.

Is PVC fill different from EMT?

Yes. Schedule 40 PVC has a slightly smaller internal area than EMT of the same trade size, so it can hold the same number of wires or fewer.