What Size Wire for a 200 Amp Service?

By Hassan Nawaz, B.Sc. Electrical Engineering. Updated November 11, 2026.

For a 200 amp single-phase dwelling service, use 2/0 copper or 4/0 aluminum service conductors and a 4 AWG copper wire to the ground rod. The table below covers every service from 100 to 400 amps. Distance and non-dwelling services follow different rules.

Service entrance wire size for 100 to 400 amps

NEC 310.12 lets the main power feeder or service conductors of a single-phase, 120/240 V dwelling be smaller than the usual ampacity tables, because dwellings rarely load every circuit at once. This is often called the 83% rule. It applies to the service conductors and feeders carrying the whole load of a one-family home, and it is for 100 to 400 A only.

ServiceCopperAluminum or copper-cladGround rod wire (copper)
100 A4 AWG2 AWG8 AWG
110 A3 AWG1 AWG8 AWG
125 A2 AWG1/0 AWG8 AWG
150 A1 AWG2/0 AWG6 AWG
175 A1/0 AWG3/0 AWG6 AWG
200 A2/0 AWG4/0 AWG4 AWG
225 A3/0 AWG250 kcmil4 AWG
250 A4/0 AWG300 kcmil2 AWG
300 A250 kcmil350 kcmil2 AWG
350 A350 kcmil500 kcmil2 AWG
400 A400 kcmil600 kcmil1/0 AWG

The last column is the grounding electrode conductor from NEC Table 250.66, sized from the copper service conductors. If it only goes to a ground rod, 250.66(A) does not require more than 6 AWG copper. To a concrete-encased electrode, 4 AWG copper is the most required.

200 amp service wire size

When the 83% rule does not apply

Outside a single-family dwelling service or feeder, size by the ampacity table. 200 A needs 3/0 copper (200 A at 75°C) or 250 kcmil aluminum (205 A) in that case. This also applies to a 200 A sub panel feeder to a detached building, and to any three-phase or commercial service.

CaseCopperAluminum
Single-family dwelling service (310.12)2/0 AWG4/0 AWG
Any other 200 A feeder (310.16, 75°C)3/0 AWG250 kcmil

Voltage drop on a long service run

A 200 A load at 240 V on 2/0 copper stays within 3% for about 186 ft one way. On 4/0 aluminum the limit is about 180 ft. A service lateral longer than that should be upsized. The ground wire then increases in proportion, under NEC 250.122(B). Check your numbers with the voltage drop calculator.

Permits and inspection. A service change needs a permit and a utility connection in nearly every jurisdiction. The wire size is only part of it: meter base, conduit size, bonding and the grounding electrode system are inspected too. Use this page to understand the numbers and have a licensed electrician confirm them for your house.

For smaller breakers, see the breaker to wire size chart.

Frequently asked questions

What size wire for 200 amp service?

2/0 copper or 4/0 aluminum for a single-phase dwelling service under NEC 310.12. Any other 200 A feeder needs 3/0 copper or 250 kcmil aluminum.

What size ground wire for 200 amp service?

4 AWG copper to the grounding electrode, when the service conductors are 2/0 copper. If it connects only to a ground rod, 6 AWG copper is enough.

What size wire for a 100 amp service?

4 AWG copper or 2 AWG aluminum for a single-phase dwelling.

What size wire for a 200 amp sub panel?

3/0 copper or 250 kcmil aluminum. The dwelling 83% rule does not apply to a sub panel in a detached building.

What size conduit for 200 amp service?

Typically 2 inch for 2/0 or 4/0 conductors, but conduit fill depends on the wire type and the number of conductors. Confirm with the NEC Annex C tables or your inspector.

Sources

Calculators for this

Last updated November 11, 2026. Values follow published tables. How we check our data. Found an error? Tell us.